Freon Gas Detector
OSC92GT300, 300B

<Features>
- Corresponds to alternative refrigerant such as R134a/404A/407C/410A and existing refrigerant such as R22, etc.
- Micro leakage can be measured by max. sensitivity of 0.5 g/year (at R410A, H5)
- Quick response of within 0.5 sec at H5 range
- Zero reset button incorporated on probe (*OSC 92GT300B only)
- Possible to fit optional fleon gas calibration device to the main body
- Auto alarm function which informs sensor wire breakage by buzzer sound and LED
- Flow meter is equipped on the panel of main body as a standard enabling to check suction status
- Easily understood detection judgement by scaled buzzer sound and the front speaker.
- External output like analog voltage output and alarm contact output incorporated as standard
- Low running cost with long service timme of sensor and less consumables


Specifications
MODEL OSC 92GT300, 300B
Objective gas Existing general fleon gases such as R12, R22, R502, R134a, R404A, R407C, R410A, R600a
Detecting method Semiconductor sensor suction method
Maximum sensitivity 5X10-6ml/sec (approx. 0.5g/year) in case of R410A
Reaction speed within 0.5 sec (at range H5, suction volume 200 mL/min)
Sensitivity range selection H/L ranges 5 steps each
Suction method Auto suction pump (max. 200 mL/min)
Leak indication Analog meter and buzzer (buzzer volume and alarm point adjustable)
Reset Button equipped on probe (OSC 92GT300B only)
Calibration device (optional) NIST authorized calibration device (optional extra) 20 g/year can be equipped
Power source AC100V-240V (50/60Hz)
External output Voltage output for recorder DC0-5V, Alarm contact output (A point AC125V 1A)
Operational environment 20±15℃  65±20%RH
Dimensions and weight 350W x 270D x 160H mm, approx. 5.4 kg
Standard accessories Standard probe (2 m) x 1, Spare fuse (3A) x 1, Cartriudge filter x 5, perfornace data sheet, operation manual, certificate of guarantee 2
Optional extra Sensor(black and blue), Probe Ass'y, Probe tube, Probe tip carbon flex, silicon seal, cartridge filter, Fuse for FER

back to top

pdf brochure
Contact Form
       Name of Product(*)
       
       Request of Quotation
       Requesf for Specifications
       ※Please fill in your message.
               
Name and Organization
       Your Name(*)
       
       Company or Organization(*)
       
       Faculty, Department or Position
       
Your Contacts
 E-Mail(*)
       
 Telephone/Skype Number